Error Messages
Error message
Cause
Possible remedy
At actual process value
maximum value flashes
Top range end has
been exceeded, sen-
sor defect
Check sensor and cable
At actual process value
minimum value flashes
Bottom range end
has been exceeded,
sensor defect
Check sensor cable
Check process value offset
TC connected with inverted polarity
REMOTE:
Parameter
locked
Adjusting of parame-
ters is not allowed.
Device is controlled
by fieldbus.
Profibus: The parameter “Remote“ in the
menu Field bus is set to “on”.
EloVision is active!
Adjusting of parame-
ters is not allowed.
Device is controlled
by EloVision.
The configuration-tool EloVision is active.
Please close EloVision, or switch to the visu-
alisation page of von EloVision.
Field bus module
unavailable
The controller is not fitted with the correct
hardware for the selected protocol.
Zone synopsis:
Current: --.-A
No current measure-
ment
Set the logic output of the corresponding
zone to heating.
DfErr
Text display error
Please send the controller back to the
manufacturer.
ERR0
System error
Please send the controller back to the
manufacturer.
ERR8
System error
Quit error message.
Check the parameters. If the error is still
there, send the controller back to the
manufacturer.
ERR IO
Error I/O board
See logbook:
Error IO board 1 or 2
Error IO board 3 or 4
The connection to the input/output circuit
board is broken.
-> Internal card defective, please send the
controller back to the manufacturer.
-> If zone extension (5.4.9.2 menu About)
is set to 12 or 16, the required additional
module R4010 may not be connected.
Switch off zone extension if necessary.
Info: All 4 sensors of the faulty card are set
to sensor break.