3.7 CMA Replacement
Figure 102:
LED Pointer Orientation
Caution:
To ensure proper airflow for enclosure cooling, all drive slots must be populated
with either drives or drive blanks.
Step 22 :
Ensure that the enclosure has been pulled out of the rack until the rail latches engage.
Step 23 :
Install each drive in the place it was removed from by following the labels or marks that were
added earlier.
Step 24 :
Align the drive with the empty slot that will receive it. Lower it into the slot, ensuring that it stays
level and does not bind.
102