User Guide
3. Support
3.8 Rails Replacement
Tool
Required vs. Recommended
Optional (if using CMA Tray):
M3 x 8mm T10 Torx screws
Recommeded
Step 1 :
Place the CMA(s) into service position.
a.
Unlatch the CMA(s) from the rail at the elbow connector by pressing the blue release button.
Figure 109:
Unlatching a CMA Connector
b.
Swing the CMA(s) away from the enclosure.
c.
The arm(s) should be extended away from the enclosure as shown in the following example.
Figure 110:
CMA(s) in service position (Cables not shown)
Step 2 :
Disconnect the Enclosure from power.
a.
Locate the redundant PSUs at the rear of the enclosure.
b.
Detach the cable retention mechanism from both power cords.
107