2.8 Retracting the Unit
To avoid injury, DO NOT stand over the sampler motor housing during retraction.
1.
Ensure that the inFlow™ ACE has been purged. See
Section 2.6, Purging the Unit,
for instructions on properly purging
the inFlow™ ACE.
2.
Deactivate or turn OFF the hydraulic or pneumatic supply.
3.
Depressurize, drain, and disconnect the hydraulic or pneumatic supply lines.
4.
Close emergency shutoff valve E (
).
5.
Disconnect the sample container from the sample outlet.
If the unit will be retracted using hydraulic fluid, continue to step 6.
If the unit will be retracted using an auxiliary gas, proceed to step 14.
If the unit will be retracted using pipeline product, proceed to step 24.