AC INVERTER PROGRAMMING INSTRUCTIONS
The WFC Series AC Inverters come wired for external use and must be installed for use in a side panel control (See
WIRING DIAGRAMS). Refer to owners manual for complete instructions and explanations. Manual used for the
following was FORM 1094.
After installation is complete the inverter must be reprogrammed to Cleveland's modifications of the factory settings. All
modifications are achieved in Access Level 2.
1.
Turn agitator power on. The top four LED indicators will illuminate momentarily - wait for the three green LED's to go
out before proceeding.
2.
Press the PROGram and SHIFT keys simultaneously to reach Access Level 2. The display display will now read:
3.
Use the UP/DOWN arrow keys to select the program parameter for change.
4.
Press the SHIFT key. The program number will blink indicating that that the data value may be changed.
5.
Use the UP/DOWN arrow keys to select the new data code.
6.
Press the ENTER key. The display will indicate **STORED** for one second, then revert to the normal parameter
display.
7.
Press the PROGram key to exit the programming mode or the UP/DOWN keys to select an new parameter for
change.
PROGRAM CODE SUMMARY:
#
Name
Description
Data Range
Factory Setting
Units
Access Level
Customer Setting
01
MODEL
Model Number
0-65000
Note 1
---
1
02
RVLVL
Software Revision
0-640
Note 1
---
2
03
IRAT
Rated Current
2-200
Note 1
A
2
05
SERNO
Serial Number
0-65000
---
---
2
06
REP
Repair Date
0-65000
---
---
2
07
FLT3
Last Fault
---
---
---
1
08
FLT2
2nd Fault
---
---
---
2
09
FLT1
1st Fault
---
---
---
2
12
FOUT
Output Frequency
0-400
---
Hz
1
13
VOUT
Output Voltage
0-100
---
%
1
14
IOUT
Output Current
0-650
---
A
1
15
LOAD
Drive Load
0-200
---
%
1
16
TORQ
Load Torque
0-200
---
%
1
17
TEMP
Inverter Temp
2-105
---
C
1
18
TIME1
Total Run Time
0-65000
---
h
2
19
TIME2
Power On Hours
0-65000
---
h
2
21
MODE
Input Mode
0-36
0
---
1
4
24
FSEL
Reference Select
0-18
0
---
2
27
TLSEL
Torque Limit Select
0-6
0
---
2
31
FMIN
Min. Frequency
0.00-400
0
Hz
1
14
32
FMAX
Max. Frequency
20.00-400
60
Hz
1
70
33
F2
Preset Speed #2 - Jog
0.00-400
5
Hz
1
34
F3
Preset Speed #3
0.00-400
20
Hz
2
35
F4
Preset Speed #4
0.00-400
40
Hz
2
36
F5
Preset Speed #5
0.00-400
60
Hz
2
37
F6
Preset Speed #6
0.00-400
0
Hz
2
38
F7
Preset Speed #7
0.00-400
0
Hz
2
39
FTL
Min. Frequency in Torque Limit
0.00-400
10
Hz
2
41
RSEL
Ramp Selector
0-7
0
---
2
42
ACC1
Acceleration Time #1
0.10-600
3
s
1
9
Содержание CLEVELAND HA-MKGL-100
Страница 30: ...29 WIRING DIAGRAM 208 240V Page 1 of 2 Continued on page 2...
Страница 31: ...30 WIRING DIAGRAM 208 240V Page 2 of 2 Continued from page 1...
Страница 32: ...31 WIRING DIAGRAM 460 480V Page 1 of 2 Continued on page 2...
Страница 33: ...32 WIRING DIAGRAM 460 480V Page 2 of 2 Continued from page 1...
Страница 59: ...TILTING MODELS STATIONARY MODELS 58 PLUMBING ASSEMBLY WATER METER...