17
TROUBLESHOOTING GUIDES
(continued)
PROBLEM:
Kettle Won't
Heat
Does red light
(
2
)
come on when unit
is first turned on?
Does red light
(
2
)
go off shortly after
unit is turned on?
Yes
Add water
to jacket of
Kettle.
No
Yes
Is 16 VAC
(
13
)
measured across
Pins 9 and 10 on
the controller
(
15
)
?
No
Yes
Is 16 VAC
(
13
)
at the
secondary side of
the transformer
No
Replace
the on/off
(
3
)
switch (toggle
or rotary).
Yes
Is there Power to
the primary of the
transformer
(
13
)
?
No
Replace the
transformer
(
13
)
.
Yes
Supply power
to the kettle.
No
Does the relay pull
in
(
1
8
)
?
Yes
Replace the
relay
(
1
8
)
.
No
Is there power to
the blower
(
8
)
?
Yes
With the high limit
(
16
)
temporarily
bypassed, is
power at the
blower
(
8
)
?
No
Replace the
high limit
(
16
)
.
Yes
Replace
the wire to
the blower
(
8
)
.
No
Is there power to
the ignition
Is there 24 VAC at
the secondary of
the ignition
transformer
(
14
)
?
transformer
(
14
)
?
Is there 24 VAC to
the igniton
module
(
17
)
?
Yes
Does the blower
(
8
)
turn?
Replace
blower
(
8
)
.
No
Yes
Yes
Replace the
DC relay
(
1
8
)
.
Replace the
ignition
transformer
(
14
).
Replace the air
switch
(
19
)
.
No
Is there 120 VAC
to the
igniter
(
11
)
?
Yes
Replace
ignition module
(
17
)
.
No
Does the ignitor
glow
(
11
)
?
Yes
Replace the
ignitor
(
11
)
.
No
No
Does the gas
valve
(
7
)
get 24 VAC
20 sec. after the
ignitor
(
11
)
is
energized?
Yes
No
Does the gas
valve
(
7
)
open?
Yes
Replace gas
valve
(
7
).
No
Yes
No
With the
potentiometer
(
4
)
set at 10,
is 12 VDC at the
coil of the relay
(
1
8
)
?
Содержание CLEVELAND HA-MKGL-100
Страница 30: ...29 WIRING DIAGRAM 208 240V Page 1 of 2 Continued on page 2...
Страница 31: ...30 WIRING DIAGRAM 208 240V Page 2 of 2 Continued from page 1...
Страница 32: ...31 WIRING DIAGRAM 460 480V Page 1 of 2 Continued on page 2...
Страница 33: ...32 WIRING DIAGRAM 460 480V Page 2 of 2 Continued from page 1...
Страница 59: ...TILTING MODELS STATIONARY MODELS 58 PLUMBING ASSEMBLY WATER METER...