Installation and Operating Manual
Page
53
Printed: 02/2015
Manual control valve for desludging (4):
A certain part of the water in the system must be drained off in order to ensure that fresh
water is continuously fed to the circuit. This manual control valve is used to adjust the
desludging rate.
It is
important
that the cells and the tray are checked approx. 2 weeks after commissioning. If
required, increase or reduce the desludging rate. Subsequent checks (and adjustments) must
be performed at least on a monthly basis.
Drain (11):
The drain (1" male thread) must be equipped by the operator with a stop valve and siphon.
The siphon outlet end must be open and must feed the water to the waste water system.
Overflow (10):
The overflow (1" male thread) must be equipped by the operator with a siphon. The siphon
outlet end must be open (no stop valve) and must feed the water to the waste water system.
The overflow must never be blocked.
2. Fresh water operation
WEGER components:
Supply line:
TACO Setter
solenoid valve open/closed
Humidifier control:
Manual, by means of flow meter + controller (TACO Setter)
Supply connection:
½" male connector
Outlet line:
1½" male connector