background image

PF4MNB

DIRECT EXPANSION

FAN COIL UNIT

Installation Instructions

FOR R410A REFRIGERANT

SIZES 019 TO 061

NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

HEATER PACKAGES

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 1 -- Check Equipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . .

Step 2 -- Mount Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 3 -- Air Ducts

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 4 -- Electrical Connections

4

. . . . . . . . . . . . . . . . . . . . . .

Step 5 -- Refrigerant Tubing Connection and Evacuation

7

. . .

Step 6 -- Refrigerant Flow--Control Device

7

. . . . . . . . . . . . . .

Step 7 -- Condensate Drains

8

. . . . . . . . . . . . . . . . . . . . . . . . .

Step 8 -- Accessories

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 9 -- Sequence of Operation

9

. . . . . . . . . . . . . . . . . . . . . .

START--UP PROCEDURES

9

. . . . . . . . . . . . . . . . . . . . . . . . . .

CARE AND MAINTENANCE

9

. . . . . . . . . . . . . . . . . . . . . . . .

AIRFLOW PERFORMANCE TABLES

10

. . . . . . . . . . . . . . . .

R--410A QUICK REFERENCE GUIDE

12

. . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury or property

damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified

installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions

packaged with kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing

and work gloves. Have a fire extinguisher available. Read these

instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local

building codes and the current editions of the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical

Code CSA C22.1.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instruction manuals,

be alert to the potential for personal injury.

Understand the signal words

DANGER

,

WARNING

, and

CAUTION

. These words are used with the safety--alert symbol.

DANGER

identifies the most serious hazards which

will

result in

severe personal injury or death.

WARNING

signifies hazards

which

could

result in personal injury or death.

CAUTION

is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage.

NOTE

is used to highlight

suggestions which will result in enhanced installation, reliability, or
operation.

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing unit, always turn off all power to

unit. There may be more than 1 disconnect switch. Turn off

accessory heater power if applicable. Lock out and tag switch

with a suitable warning label.

!

WARNING

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate protective clothing and gloves when

handling parts.

CAUTION

!

INTRODUCTION

Model PF4MNB Fan Coils are designed for flexibility and can be

used for upflow, horizontal, or downflow (kit required) and
manufactured and mobile home applications. These units are

designed to meet the low air leak requirements currently in effect.

Because of this, the units need special attention in the condensate
pan and drain connection area and when brazing tubing. These

units are designed specifically for R--410A refrigerant and must be
used only with R--410A refrigerant air conditioners and heat

pumps as shipped. These units are available for systems of 18,000

through

60,000

Btuh

nominal

cooling

capacity.

Factory--authorized, field--installed electric heater packages are

available in sizes 5 through 30kW. See Product Data literature for
available accessory kits.

HEATER PACKAGES

Factory--approved, field--installed, UL listed heater packages are
available from your equipment supplier. See unit rating plate for a

list of factory--approved heaters. Heaters that are not factory

approved could cause damage which would not be covered under
the equipment warranty.

Содержание PF4MNB 019

Страница 1: ...d with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death...

Страница 2: ...ng with an accessory base kit Use fireproof resilient gasket 1 8 to 1 4 in 3 to 6 mm thick between duct unit and floor UNIT OR PROPERTY DAMAGE HAZARD Failure to follow this caution may result in produ...

Страница 3: ...h condensate pan down See Fig 5 5 Attach coil to casing flange using coil mounting screw pre viously removed 6 Make sure the pan cap in the fitting door is properly seated on the fitting door to retai...

Страница 4: ...fan coil b If fan coil is against wall secure fan coil to wall stud using 1 8 in 3 mm thick right angle brackets Attach brackets to fan coil using no 10 self tapping screws and to wall stud using 5 1...

Страница 5: ...er plug from fan coil and connect male plug from heater to female plug from unit wiring harness See Electric Heater Installation Instructions For units without electric heater 1 Connect 208 230v power...

Страница 6: ...factory wired for 230v operation For 208v applications disconnect the black wire from the 230v terminal on transformer and connect it to the 208v terminal See Fig 15 2 3 0 C 2 0 8 BRN RED YEL BLK SEC...

Страница 7: ...p 5 Max 0 sec off delay electric heat airflow is same CFM as Tap 3 except 0 sec off delay high static applications see airflow tables for max airflow To change motor speeds disconnect the BLUE fan lea...

Страница 8: ...vertical pan fitting to door joint to retain the low air leak performance of the unit CAUTION Units are equipped with primary and secondary 3 4 in FPT drain connections For proper condensate line ins...

Страница 9: ...o Y and R to O heat pump only G energizes fan relay on PCB which completes circuit to indoor blower motor When G is de energized there is a 90 second delay before fan relay opens NOTE Speed taps 1 2 a...

Страница 10: ...33 Tap 1 1237 1206 1160 1121 1070 1013 PF4MNB 049 Tap 5 1757 1725 1693 1653 1614 1576 Tap 4 1664 1626 1593 1552 1517 1477 Tap 3 1664 1626 1593 1552 1517 1477 Tap 2 1459 1420 1379 1336 1298 1259 Tap 1...

Страница 11: ...0 016 0 027 0 038 0 049 0 059 031 0 049 0 059 0 070 0 080 037 0 055 0 064 0 073 0 081 043 0 049 0 056 0 063 0 070 049 0 038 0 043 0 049 0 054 0 059 061 0 027 0 031 0 035 0 039 0 043 Table 3 Electric H...

Страница 12: ...nstall a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all fi...

Отзывы: