2

INSTALLATION

Step 1 — Check Equipment

Unpack unit and move to final location. Remove carton taking care
not to damage unit. Inspect equipment for damage prior to

installation. File claim with shipping company if shipment is
damaged or incomplete.
Locate unit rating plate which contains proper installation

information. Check rating plate to be sure unit matches job
specifications.

Step 2 — Mount Unit

Unit can stand or lie on floor, or hang from ceiling or wall. Allow
space for wiring, piping, and servicing unit.

IMPORTANT

: When unit is installed over a finished ceiling

and/or living area, building codes may require a field--supplied
secondary condensate pan to be installed under the entire unit.
Some localities may allow as an alternative, the running of a
separate, secondary condensate line. Consult local codes for
additional restrictions or precautions.

NOTE

: Nuisance sweating may occur if the unit is installed in a

high humidity environment with low airflow.

A. Upflow Installation

If return air is to be ducted through a floor, set unit on floor over

opening and use 1/8 to 1/4--in (3 to 6 mm) thick fireproof resilient
gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening per
dimensions. (See Fig. 1.) A field--supplied bottom closure is

required.

A COIL

UNITS

POWER ENTRY

OPTIONS

LOW VOLT
ENTRY
OPTIONS

FIELD MODIFIED
SIDE RETURN
LOCATION FOR
SLOPE COIL
UNITS ONLY

FIELD SUPPLIED
RETURN PLENUM

UPFLOW/DOWNFLOW

SECONDARY DRAIN

UPFLOW/DOWNFLOW

PRIMARY DRAIN

019, 025

17" (432 mm)

A

1.5" (38 mm) 

   2.5"
(64 mm) 

19" (483 mm)

FIELD SUPPLIED
SUPPLY DUCT

UPFLOW/DOWNFLOW

SECONDARY DRAIN

UPFLOW/DOWNFLOW

PRIMARY DRAIN

     031

19" (483 mm)

019 - 049  21" (533 mm) FRONT SERVICE
     061      24" (610mm)  CLEARANCE

UNIT

A

A09382

Fig. 1 -- Slope Coil Unit in Upflow Application

B. Downflow Installation

In this application, field conversion of the evaporator is required

using accessory downflow kit along with an accessory base kit.
Use fireproof resilient gasket, 1/8 to 1/4--in (3 to 6 mm) thick,

between duct, unit, and floor.

UNIT OR PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in product or property

damage.
The conversion of the fan coil to downflow requires special

procedures for the condensate drains on both A--coil and slope

units. The vertical drains have an overflow hole between the

primary and secondary drain holes. This hole is plugged for all

applications except downflow, but must be used for downflow.

During the conversion process, remove the plastic cap

covering the vertical drains only and discard. Remove the plug

from the overflow hole and discard. At completion of the

downflow installation, caulk around the vertical pan fitting to

door joint to retain the low air leak performance of the unit.

CAUTION

!

NOTE

: To convert units for downflow applications, refer to

Installation Instructions supplied with kit for proper installation.
For slope fan coils, use kit Part No. KFADC0201SLP. For A--coils,
use kit Part No. KFADC0401ACL. Use fireproof resilient gasket,
1/8 to 1/4--in (3 to 6 mm) thick, between duct, unit, and floor.

NOTE

: Gasket kit number KFAHD0101SLP is also required for

all downflow applications to maintain low air leak/low sweat
performance.

C. Horizontal Installation

Units must not be installed with access panels facing up or down.

All other units are factory built for horizontal left installation. (See
Fig. 2 and 3.) When suspending unit from ceiling, dimples in

casing indicate suitable location of screws for mounting metal
support straps. (See Fig. 2.)
For horizontal applications having high return static and humid

return air, the Water Management Kit, KFAHC0125AAA, may
need to be used to assist in water management.

UNIT

FIELD
SUPPLIED
HANGING
STRAPS

LOW VOLT
ENTRY
OPTIONS

POWER
ENTRY OPTIONS

SECONDARY
DRAIN

018-048   21" (533 mm)
060-060   24" (610 mm) 
FRONT SERVICE
CLEARANCE
(FULL FACE
OF UNIT)

SECONDARY
DRAIN

A-COIL

HORIZONTAL LEFT

PRIMARY
DRAIN

PRIMARY
DRAIN

1.75" (44 mm) 
FILTER ACCESS
CLEARANCE

A07566

Fig. 2 -- Slope Coil Unit in Horizontal Left Application

PF4M

NB

Содержание PF4MNB 019

Страница 1: ...d with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death...

Страница 2: ...ng with an accessory base kit Use fireproof resilient gasket 1 8 to 1 4 in 3 to 6 mm thick between duct unit and floor UNIT OR PROPERTY DAMAGE HAZARD Failure to follow this caution may result in produ...

Страница 3: ...h condensate pan down See Fig 5 5 Attach coil to casing flange using coil mounting screw pre viously removed 6 Make sure the pan cap in the fitting door is properly seated on the fitting door to retai...

Страница 4: ...fan coil b If fan coil is against wall secure fan coil to wall stud using 1 8 in 3 mm thick right angle brackets Attach brackets to fan coil using no 10 self tapping screws and to wall stud using 5 1...

Страница 5: ...er plug from fan coil and connect male plug from heater to female plug from unit wiring harness See Electric Heater Installation Instructions For units without electric heater 1 Connect 208 230v power...

Страница 6: ...factory wired for 230v operation For 208v applications disconnect the black wire from the 230v terminal on transformer and connect it to the 208v terminal See Fig 15 2 3 0 C 2 0 8 BRN RED YEL BLK SEC...

Страница 7: ...p 5 Max 0 sec off delay electric heat airflow is same CFM as Tap 3 except 0 sec off delay high static applications see airflow tables for max airflow To change motor speeds disconnect the BLUE fan lea...

Страница 8: ...vertical pan fitting to door joint to retain the low air leak performance of the unit CAUTION Units are equipped with primary and secondary 3 4 in FPT drain connections For proper condensate line ins...

Страница 9: ...o Y and R to O heat pump only G energizes fan relay on PCB which completes circuit to indoor blower motor When G is de energized there is a 90 second delay before fan relay opens NOTE Speed taps 1 2 a...

Страница 10: ...33 Tap 1 1237 1206 1160 1121 1070 1013 PF4MNB 049 Tap 5 1757 1725 1693 1653 1614 1576 Tap 4 1664 1626 1593 1552 1517 1477 Tap 3 1664 1626 1593 1552 1517 1477 Tap 2 1459 1420 1379 1336 1298 1259 Tap 1...

Страница 11: ...0 016 0 027 0 038 0 049 0 059 031 0 049 0 059 0 070 0 080 037 0 055 0 064 0 073 0 081 043 0 049 0 056 0 063 0 070 049 0 038 0 043 0 049 0 054 0 059 061 0 027 0 031 0 035 0 039 0 043 Table 3 Electric H...

Страница 12: ...nstall a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all fi...

Отзывы: