TECHNICAL SPECIFICATIONS
8.1.5 Current, Motor and Loss Data
Table 8.5:
Current, power and loss data for B2 and T2 lines and “ND” overload class
ND overload class:
110% for 60 seconds with a 5-minute interval
150% for 3 seconds with a 5-minute interval
Inverter loss data as
per IEC61800-9-2
(1)
Inverter model
Typical motor
(2)
Dissipated power
for sizing the
panel
Rated
apparent
power
Rated
output
current
220V/60Hz
230V/50Hz
230V/60Hz
NEC
Table
208V
NEC
Table
230V
Inverter
complete
Front
part
230V
Losses at
rated condition
/
Apparent power
Io,nom (ND)
P,nom
P,nom
P,nom
P,nom
P,nom
PL(inv)
PL(inv2)
So
pL( 90,100)
[Arms]
[CV]
[kW]
[hp]
[hp]
[hp]
[W]
[W]
[kVA]
[%]
CFW900A04P6B2
4.6
1.5
1.1
1.5
1
1
81
34
1.8
4.4%
CFW900A06P0B2
6
2
1.5
2
1
1.5
96
39
2.4
4.1%
CFW900A07P5B2
7.5
2
1.5
3
2
2
109
41
3.0
3.7%
CFW900A10P0B2
10
3
2.2
3
2
3
127
46
4.0
3.2%
CFW900A04P6T2
4.6
1.5
1.1
1.5
1
1
70
30
1.8
3.9%
CFW900A06P0T2
6
2
1.5
2
1
1.5
84
32
2.4
3.5%
CFW900A07P5T2
7.5
2
1.5
3
2
2
92
34
3.0
3.1%
CFW900A10P6T2
10.6
3
3
3
3
3
111
36
4.2
2.7%
CFW900A13P0T2
13
4
3
5
3
3
130
39
5.2
2.5%
CFW900A19P0T2
19
6
5.5
7.5
5
5
168
45
7.6
2.3%
CFW900B26P0T2
26
10
7.5
10
7.5
7.5
251
64
10.4
2.5%
CFW900B34P0T2
34
12.5
9.2
10
10
10
315
75
13.5
2.4%
CFW900B45P0T2
45
15
11
15
10
15
420
90
17.9
2.4%
CFW900C56P0T2
56
20
15
20
15
20
538
114
22.3
2.5%
CFW900C70P0T2
70
25
18.5
25
20
25
627
128
27.9
2.3%
CFW900C80P0T2
80
30
22
30
25
30
710
142
31.9
2.3%
CFW900D0110T2
110
40
30
40
30
40
956
172
43.8
2.2%
CFW900D0135T2
135
50
37
50
40
50
1192
208
53.8
2.3%
CFW900D0150T2
150
60
45
60
50
50
1363
233
59.8
2.3%
CFW900E0172T2
172
60
55
75
60
60
1629
300
68.5
2.4%
CFW900E0195T2
195
75
55
75
60
75
1897
337
77.7
2.5%
CFW900E0250T2
250
100
75
100
75
100
2375
402
99.6
2.4%
(1)
Inverter efficiency rating: see
. Inverter losses at the other seven operating points specified by IEC61800-9-2 standard: see
specific document on Ecodesign Directive. To determine losses for different motors, use the WEG Ecodrive app.
(2)
Rated power values defined based on the rated current of WEG motors at the indicated voltages.
indicates the maximum inverter
ambient temperature considered for choosing the motor.
98 | CFW900