English
INSTALLATION AND CONNECTION
Table 3.4:
Recommended wire size - Use only copper wire (75 ºC (167 °F))
Power Terminals
Wire size
Model
Terminals
Screw
(type)
Recommended
Torque
N.m (Ibf.in)
mm²
AWG
Terminal type
Power
(1)
M4
(phillips/ slotted)
Fork
CFW900A04P6B2
Grounding
(2)
M4
(phillips)
1.2 (10.6)
2.5
14
Lug
Power
(1)
M4
(phillips/ slotted)
Fork
CFW900A06P0B2
Grounding
(2)
M4
(phillips)
1.2 (10.6)
2.5
14
Lug
Power
(1)
M4
(phillips/ slotted)
2.5/4
(3)
14/12
(3)
Fork
CFW900A07P5B2
Grounding
(2)
M4
(phillips)
1.2 (10.6)
4.0
12
Lug
Power
(1)
M4
(phillips/ slotted)
2.5/6
(3)
14/10
(3)
Fork
CFW900A10P0B2
Grounding
(2)
M4
(phillips)
1.2 (10.6)
6.0
10
Lug
Power
(1)
M4
(phillips/ slotted)
Fork
CFW900A04P6T2
Grounding
(2)
M4
(phillips)
1.2 (10.6)
2.5
14
Lug
Power
(1)
M4
(phillips/ slotted)
Fork
CFW900A06P0T2
Grounding
(2)
M4
(phillips)
1.2 (10.6)
2.5
14
Lug
Power
(1)
M4
(phillips/ slotted)
Fork
CFW900A07P5T2
Grounding
(2)
M4
(phillips)
1.2 (10.6)
2.5
14
Lug
Power
(1)
M4
(phillips/ slotted)
Fork
CFW900A10P6T2
Grounding
(2)
M4
(phillips)
1.2 (10.6)
2.5
14
Lug
(1)
R/L1 ; S/L2 ; T/L3 ; U/T1 ; V/T2 ; W/T3 ; DC+ ; DC-.
(2)
PE.
(3)
The first value is for 3-phase power supply and motor connection, and the second value is for single-phase power supply.