TECHNICAL SPECIFICATIONS
Table 8.6:
Current, power and loss data for B2 and T2 lines and “HD” overload class
HD overload class:
150% for 60 seconds with a 5-minute interval
200% for 3 seconds with a 5-minute interval
Inverter loss data as
per IEC61800-9-2
(1)
Inverter model
Typical motor
(2)
Dissipated power
for sizing the
panel
Rated
apparent
power
Rated
output
current
220V/60Hz
230V/50Hz
230V/60Hz
NEC
Table
208V
NEC
Table
230V
Inverter
complete
Front
part
230V
Losses at
rated condition
/
Apparent power
Io,nom (HD)
P,nom
P,nom
P,nom
P,nom
P,nom
PL(inv)
PL(inv2)
So
pL( 90,100)
[Arms]
[CV]
[kW]
[hp]
[hp]
[hp]
[W]
[W]
[kVA]
[%]
CFW900A04P6B2
4.6
1.5
1.1
1.5
1
1
81
34
1.8
4.4%
CFW900A06P0B2
6
2
1.5
2
1
1.5
96
39
2.4
4.1%
CFW900A07P5B2
7.5
2
1.5
2
2
2
109
41
3
3.7%
CFW900A10P0B2
10
3
2.2
3
2
3
127
46
4
3.2%
CFW900A04P6T2
4.6
1.5
1.1
1.5
1
1
70
30
1.8
3.9%
CFW900A06P0T2
5
1.5
1.5
2
1
1
73
31
2
3.7%
CFW900A07P5T2
6.8
2
1.5
2
1.5
2
85
33
2.7
3.2%
CFW900A10P6T2
9.6
3
2.2
3
2
3
102
35
3.8
2.7%
CFW900A13P0T2
11
3
3
3
3
3
111
37
4.4
2.6%
CFW900A19P0T2
16
5
4
5
3
5
143
42
6.3
2.3%
CFW900B26P0T2
22
7.5
5.5
7.5
5
7.5
212
59
8.7
2.5%
CFW900B34P0T2
28
10
7.5
10
7.5
10
260
67
11.1
2.4%
CFW900B45P0T2
35
12.5
9.2
10
10
10
320
76
13.9
2.3%
CFW900C56P0T2
47
15
11
15
15
15
447
103
18.7
2.4%
CFW900C70P0T2
59
20
15
25
15
20
523
115
23.5
2.3%
CFW900C80P0T2
70
25
18.5
30
20
25
614
129
27.9
2.2%
CFW900D0110T2
92
30
22
30
30
30
784
148
36.6
2.2%
CFW900D0135T2
110
40
30
40
30
40
942
172
43.8
2.2%
CFW900D0150T2
124
50
37
50
40
40
1081
192
49.4
2.2%
CFW900E0172T2
150
60
45
60
50
50
1391
267
59.7
2.4%
CFW900E0195T2
160
60
45
60
50
60
1497
281
63.7
2.4%
CFW900E0250T2
211
75
55
75
75
75
1934
342
84
2.4%
(1)
The dissipated power for sizing the panel must be considered the same specified for the ND overload class according to
(2)
Rated power values defined based on the rated current of WEG motors at the indicated voltages.
indicates the maximum inverter
ambient temperature considered for choosing the motor.
CFW900 | 99