TECHNICAL SPECIFICATIONS
8.1.4
Environmental and Mechanical Data
Table 8.4:
Inverter Environmental and Mechanical Data
Inverter smart code - item ”II”
Frame suffix (inverter cabinet size)
A
B
C
D
E
Maximum operating ambient temperature
without output current derating
-Back
(1)(2)
50 °C (122 °F)
50 °C (122 °F)
50 °C (122 °F)
50 °C (122 °F)
45 °C (113 °F)
-Front
(3)
60 °C (140 °F)
60 °C (140 °F)
60 °C (140 °F)
(4)
60 °C (140 °F)
(4)
60 °C (140 °F)
Maximum operating temperature
with output current derating
-Back
(1)(2)
60 °C (140 °F)
-Front
(3)
60 °C (140 °F)
Minimum operating ambient temperature
-10 °C (14 °F)
Humidity
5 ... 95 % non-condensing
Pollution degree
2 (EN50178 / IEC61800-5-1 / UL61800-5-1)
Degree of protection
Back
IP55 / UL type 12
Front:
-Inverters with suffix ”20”
IP20 / open chassis
-Inverters with suffix ”21” or inverters
with suffix ”20” with IP21 kit
IP21 / open chassis
-Inverters with suffix ”N1” or inverters
with suffix ”20” with UL type 1 kit
UL type 1
HMI installed on metal panel
using the CFW900-RHMIF kit
IP65 / UL type 12
Altitude
Rated: 1000 m
Maximum: 4000 m with derating factor
Heatsink fan flow at the operation point
CFM
20
40
130
190
270
I/s
9
19
61
90
127
m
3
/min
0.6
1.1
3.7
5.4
7.6
Wiring supported on the power terminals
-min (mm
2
/AWG)
0.5/20
0.5/20
0.5/20
-max (mm
2
/AWG)
6/10
16/6
35/2
Cable with
M8 terminal
maximum
24 mm wide
Cable with
M10 terminal
maximum
30 mm wide
Weight (kg / lb)
4.5 / 9.9
10.0 / 22.0
20.5 / 45.2
33.5 / 73.8
63.5 / 140.0
RoHS
Yes
Conformal coating
-Inverter in standard configuration
3C2 (IEC 60721-3-3:2002)
-Inverter with suffix ”HEC”
3C3 (IEC 60721-3-3:2002)
(1)
Heatsink air inlet temperature.
(2)
If the 2 parts of the inverter are in the same environment, this is the maximum temperature around the inverter.
(3)
If the 2 parts of the inverter are installed in different compartments (flange mounting), this is the maximum temperature around the front of
the inverter.
(4)
Exception: models CFW900C74P0T4 and CFW900D0146T4 that have specification of 55 °C (131 °F). For operation above 55 °C it is
necessary to apply derating of 2 %/°C.
CFW900 | 97