Advanced Settings (LMLS-600)
Recomm Delay
The time that must elapse,
with the open-loop light
level remaining below
the Recommissioning
Threshold, before
Recommissioning starts.
Range: 0 to 240 min
Enable Diagnostic Messages:
Controls reporting of
diagnostic information,
visually and over the DLM
IRB. Select “LED” (default)
to enable the red LED
fl ash pattern indicating
Occupant Interference.
Choose “None” to disable
the red LED indication and
all other messages. Select “All” only if so directed by
WattStopper technicians.
Send
When you have completed adjusting the settings,
choose SEND.
Press Left/Right arrow
to raise or lower
Recomm Time Delay
<0min - 240min>
D a y l i g h t i n g L M L S - 6 0 0
M a x E L L i g h t :
D a y l i g h t R a t i o :
F o r c e O p e n L o o p :
R e c o m m T h r e s h :
R e c o m m D e l a y :
E n a b D i a g M s g s
N E X T
S E N D
1 . 8 3 3 f c
0 . 0 7 6 2
< Ye s >
< 1 0 f c >
< 2 0 m i n >
< A l l >
Press Left/Right arrow
to choose
D a y l i g h t i n g L M L S - 6 0 0
M a x E L L i g h t :
D a y l i g h t R a t i o :
F o r c e O p e n L o o p :
R e c o m m T h r e s h :
R e c o m m D e l a y :
E n a b D i a g M s g s
N E X T
S E N D
1 . 8 3 3 f c
0 . 0 7 6 2
< Ye s >
< 1 0 f c >
< 2 0 m i n >
< A l l >