51
Zone Settings (LMLS-400 Only)
The ON Setpoint values available for manual
adjustment are: 1.0, 1.2, 1.5, 1.8, 2.2, 2.7, 3.3, 4.0,
5.0, 6.0, 7.5, 9.0, 11, 13, 16, 20, 25, 30, 35, 45, 60,
90, 125, 180, 250, 325, 400, 475, 550, 625, 700, 775
and 850 footcandles; note that calibration can
automatically select a value not in this list.
OFF Setpoint
The target illuminance
level at the sensor,
above which the
photosensor turns the
lights OFF.
The OFF Setpoint
corresponds to the ON
Setpoint multiplied by
1.25,
1.50, 1.75 or 2.0. This
ensures that the OFF
Setpoint is always higher than the On Setpoint.
ON Time Delay
The time interval that
must elapse, with the
measured level below
the ON Setpoint,
before the controlled
lights turn on.
Range: 1 sec to 60
sec.
D a y l i g h t i n g L M L S - 4 0 0
B i - L e v e l
S E N D
O N S e t p o i n t :
O F F S e t p o i n t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 7 . 5 f c >
< 1 1 f c >
< 2 0 s e c >
< 1 0 m i n >
Press Left/Right arrow
to raise or lower
OFF Setpoint footcandles
D a y l i g h t i n g L M L S - 4 0 0
B i - L e v e l
S E N D
O N S e t p o i n t :
O F F S e t p o i n t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 7 . 5 f c >
< 1 1 f c >
< 2 0 s e c >
< 1 0 m i n >
Press Left/Right arrow
to raise or lower
ON Time Delay <1sec - 60sec>