61
Zone Settings (LMLS-600 Only)
OFF Setpoint
The target illuminance
level above which the
LMLS-600 turns the lights
OFF.
The OFF Setpoint
corresponds to the ON
Setpoint multiplied by
1.25, 1.50, 1.75 or 2.0.
This ensures that the OFF Setpoint is always higher
than the ON Setpoint.
ON Time Delay
The time interval that
must elapse, with the
measured level below the
ON Setpoint, before the
controlled lights turn ON.
Range: 15 sec to 60 sec.
OFF Time Delay
The time interval that
must elapse, with the
measured level above
the OFF Setpoint, before
the controlled lights turn
OFF.
Range: 3 min to 30 min.
Press Left/Right arrow
to raise or lower
OFF Setpoint footcandles
O N S e t p t :
O F F S e t p t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 0 . 3 0 0 f c >
< 0 . 5 2 5 f c >
< 2 0 s e c >
< 1 0 m i n >
D a y l i g h t i n g L M L S - 6 0 0
B i - L e v e l
S E N D
Press Left/Right arrow
to raise or lower
ON Time Delay <15 sec - 60 sec>
O N S e t p t :
O F F S e t p t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 0 . 3 0 0 f c >
< 0 . 5 2 5 f c >
< 2 0 s e c >
< 1 0 m i n >
D a y l i g h t i n g L M L S - 6 0 0
B i - L e v e l
S E N D
Press Left/Right arrow
to raise or lower
OFF Time Delay <3min - 30min>
O N S e t p t :
O F F S e t p t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 0 . 3 0 0 f c >
< 0 . 5 2 5 f c >
< 2 0 s e c >
< 1 0 m i n >
D a y l i g h t i n g L M L S - 6 0 0
B i - L e v e l
S E N D