Calibration (LMLS-500 Only)
CALIBRATION (LMLS-500 ONLY)
Calibration allows you to establish a relationship
between the workplane illuminance and the
measured daylight at the photocell.
Use the LMCT-100 for the Calibration process.
1. Complete all wiring and turn power ON to the
connected room controllers.
2. Select the LMLS-500 to be calibrated using the LMCT-
100.
3. Select Calibration. For each Zone, choose a
reference location that is most likely to have the
lowest light level when daylit for each zone.
Light Level at Photocell
0
20
40
60
80
100
0
500
1000
1500
2000
1750
70
L
ight
L
e
ve
l a
t T
a
s
k