Network settings
NETWORK SETTINGS
Network Settings allows viewing and changing
settings in the LMBC-300 Network Bridge Module
necessary for communication with the LMSM-
201/603 Segment Manager or a BACnet-based
Building Automation System (BAS) network. It can
be used to query the DLM Local Network bridge
(LMBC-300 or LMRC-3xx room controller) for
device information and adjustment of network
communication parameters.
The Segment Manager
communicates with the
DLM local networks and
panels over a BACnet-
compatible digital
segment network. The
LMSM-201 supports
one segment network while the LMSM-603 supports
three segment networks.
BACnet MS/TP, baud rate 9600, 19200, 38400, 76800
or 115200 selectable
Press
Select
L M B C - 3 0 0 0 0 1 6 7 8 7 2 2 9
N a m e :
0 0 1 6 7 8 7 2 2 9
D e v i c e I D : 0 0 8 6 2 2 9
A u t o S e t M S T P M A C : < Ye s >
A u t o M S T P M A C : 0 9 9
B a u d R a t e : < 3 8 4 0 0 >
M a x M a s t e r : < 1 2 7 >
S E N D
A d j u s t L i g h t L e v e l
N e t w o r k S e t t i n g s
U t i l i t i e s
M o r e
=
B AT
Press
Select
Press
Select
S e n s o r C o n fi g u r a t i o n
L o a d C o n fi g ( P n L )
D a y l i g h t i n g C o n fi g
B u t t o n C o n fi g u r a t i o n
D i m m i n g C o n fi g u r a t i o n
M o r e
=
B AT