42
Calibration (LMLS-400 Only)
Day Setup
Make this adjustment when there is enough
daylight to provide 40% to 90% of the target
light level. For example, if the target is 40
footcandles, make this adjustment when the
daylight contribution is between 16 and 36
footcandles.
1. Press the Day button.
2. Using a light meter at the task surface, press
the Up and Down LMCT-100 arrows to adjust
light levels.
3. Once the target level has been reached, press
the Select button to hold the value.
4. When Day and Night adjustments are
complete, press HOME to terminate the
calibration process and return to normal
operation.
To set the desired light level, point to the LMLS-
400 and continue pointing to it while pressing
the
/
keys. The
key increments and
the
key decrements the light level.