Zone Settings (LMLS-500 Only)
OFF Setpoint
The target illuminance level
above which the LMLS-500
turns the lights OFF.
The OFF Setpoint
corresponds to the ON
Setpoint multiplied by 1.25,
1.50, 1.75 or 2.0.
This ensures that the OFF Setpoint is always higher
than the ON Setpoint.
ON Time Delay
The time interval that must
elapse, with the measured
level below the ON Setpoint,
before the controlled lights
turn ON.
Range: 1 sec to 60 sec.
OFF Time Delay
The time interval that
must elapse, with the
measured level above the
OFF Setpoint, before the
controlled lights turn OFF.
Range: 3 min to 30 min.
Press Left/Right arrow
to raise or lower
ON Time Delay <1sec - 60sec>
O N S e t p o i n t :
O F F S e t p o i n t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 3 5 f c >
< 5 3 f c >
< 2 0 s e c >
< 1 0 m i n >
D a y l i g h t i n g L M L S - 5 0 0
Z o n e 1
B i - L e v e l
S E N D N E X T Z O N E D O N E
Press Left/Right arrow
to raise or lower
OFF Time Delay <3min - 30min>
O S e t p o i n t :
O F F S e t p o i n t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 7 . 5 f c >
< 1 1 f c >
< 2 0 s e c >
< 1 0 m i n >
D a y l i g h t i n g L M L S - 5 0 0
Z o n e 1
B i - L e v e l
S E N D N E X T Z O N E D O N E
Press Left/Right arrow
to raise or lower
OFF Setpoint footcandles
O N S e t p o i n t :
O F F S e t p o i n t :
O N T i m e D e l a y :
O F F T i m e D e l a y :
< 3 5 f c >
< 5 3 f c >
< 2 0 s e c >
< 1 0 m i n >
D a y l i g h t i n g L M L S - 5 0 0
Z o n e 1
B i - L e v e l
S E N D N E X T Z O N E D O N E