Benchmark Platinum-Edge: Operation-Service Manual
SECTION 9 – AERTRIM OPERATION
OMM-0137_D • GF-211
•
7/16/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 127 of 146
BMK 2500 AERtrim Values
MENU ITEM
Minimum
Maximum
Default
Settle Time
0
120 Sec
20 Sec
Trim Gain
0.1
5.0
0.250
Max Tries
0
100
15
O
2
Target
(must be
between O
2
Upper & O
2
Lower)
16%
3%
8%
5.5%
30%
3%
8%
6.5%
40%
3%
8%
7.0%
50%
3%
8%
6.0%
70%
3%
8%
6.0%
100%
3%
8%
5.0%
O
2
Lower
(must be at
least 1%
lower than
O
2
Upper)
16%
2.5%
5.5%
5.0%
30%
2.5%
5.5%
4.5%
40%
2.5%
5.5%
5.0%
50%
2.5%
5.5%
5.5%
70%
2.5%
5.5%
5.5%
100%
2.5%
5.5%
4.5%
O
2
Upper
(must be at
least 1%
higher than
O
2
Lower)
16%
5.5%
8.5%
6.0%
30%
5.5%
8.5%
7.0%
40%
5.5%
8.5%
7.5%
50%
5.5%
8.5%
6.5%
70%
5.5%
8.5%
6.5%
100%
5.5%
8.5%
5.5%
O
2
Offset
-3.0
3.0
1.0
BMK 2500 AERtrim Adjustment Range
CALIBRATION POINT
BLOWER VOLTAGE
Minimum
Maximum
Default
16%
1.90
2.90
2.20
30%
3.00
4.90
4.10
40%
3.70
5.90
4.80
50%
4.20
6.40
5.30
70%
5.20
8.40
6.80
100%
6.50
9.20
8.50