Benchmark Platinum-Edge: Operation-Service Manual
SECTION 9 – AERTRIM OPERATION
OMM-0137_D • GF-211
•
7/16/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 123 of 146
9.5 AERtrim MENU VALUES and DEFAULTS
The AERtrim menus are in:
Main Menu
Advanced Setup
Performance
AERtrim
AERtrim Settings
and are described the
Edge Controller Manual
(GF-213), Section 6.6.1.
BMK 750 AERtrim Values
MENU ITEM
Minimum
Maximum
Default
Settle Time
0
120 Sec
20 Sec
Trim Gain
0.1
5.0
0.250
Max Tries
0
100
15
O
2
Target
(must be
between
O
2
Upper &
O
2
Lower)
18%
3%
8%
5.5%
30%
3%
8%
5.5%
45%
3%
8%
5.5%
60%
3%
8%
5.5%
80%
3%
8%
5.5%
100%
3%
8%
5.0%
O
2
Lower
Limit
(must be at
least 1%
lower than
O
2
Upper)
18%
2.5%
5.5%
4.5%
30%
2.5%
5.5%
4.5%
45%
2.5%
5.5%
4.5%
60%
2.5%
5.5%
5.0%
80%
2.5%
5.5%
5.0%
100%
2.5%
5.5%
4.5%
O
2
Upper
Limit
(must be at
least 1%
higher than
O
2
Lower)
18%
5.5%
8.5%
6.5%
30%
5.5%
8.5%
6.5%
45%
5.5%
8.5%
6.5%
60%
5.5%
8.5%
6.0%
80%
5.5%
8.5%
6.0%
100%
5.5%
8.5%
5.5%
O
2
Offset
-3.0
3.0
1.0
BMK 750 AERtrim Adjustment Range
CALIBRATION POINT
BLOWER VOLTAGE
Minimum
Maximum
Default
18%
1.75
2.85
2.10
30%
1.95
2.60
2.55
45%
2.35
3.60
3.10
60%
3.00
3.90
3.50
80%
3.80
4.75
4.60
100%
4.75
6.00
5.60