Benchmark Platinum-Edge: Operation-Service Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
OMM-0137_D • GF-211
•
7/16/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 96 of 146
OPTION 7
Instructions: Remote Setpoint, Modbus Header Sensor & 4-20ma Setpoint Drive
Step 3: OPTION 7 CONFIGURATION
On All Boiler:
1. Go to:
Main Menu
Advanced Setup
BST Cascade
Cascade Configuration
:
•
Set the
Unit Mode
parameter to
BST Client
.
2. Go to:
Main Menu
Advanced Setup
BST Cascade
Application Configuration
:
•
Set the
Unit Address
parameter to the communication address of the unit.
On the Manager only
:
1. Go to
Main Menu
Advanced Setup
BST Cascade
, set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Parameters
Values
Cascade
Configuration
Unit Mode
BST Manager
Hdr Temp Sensor
Network
Sensor
Comm Address
240
Hdr Temp Point
14
Application
Configuration
Application
Space Heating
SH Operating Mode
Rmt Setpt Analog
BST Remote Signal
4-20mA/1-5V *
Cascade Comm
Min address
The
minimum
unit address in the cascade
Max address
The
maximum
unit address in the cascade
Cascade Baud Rate
The baud rate for the cascade.
* Be sure that the SW1-4 DIP switch on Controller’s Interface Board is set appropriately (On = Current,
Off = Voltage.)