CLS200 Series User’s Guide
Chapter 2: Installation
30
4. Use the ground connector on TB2 for chassis ground. This terminal is connected to the
CLS200 chassis and must be connected to earth ground.
5. Connect 120/240VAC power to the power supply.
NOTE!
Connect the dc common of the power supply used for loads to the dc common
of the supply powering the controller. If the supplies are not referenced to one another,
the controller’s outputs will not be able to switch the loads.
NOTE!
When making screw terminal connections, tighten to 4.5 to 5.4 inch-pound
(0.5 to 0.6 Nm).
CAUTION!
Without proper grounding, the CLS200 may not operate properly or may be
damaged.
CAUTION!
To prevent damage from incorrect connections, do not turn on the ac power
before testing the connections as explained in
Testing Your System on page 31
NOTE!
Do not connect the controller’s dc common (COM) to earth ground. Doing so will
defeat the noise protection circuitry, making measurements less stable.
** Connect terminals to ac panel ground.
SSR
SSR
SSR
SSR
G
N
D
Add jumper *
C
O
M
+
5
Serial DAC
CLS200
Power Supply
1 2 3 4
white
black
green
G
H
N
120/240
Supply
**
**
* If using 5VDC for outputs, jumper 5V common to 15V common.
C
O
M
V
+
VAC
+V1 (5V)
0 (5V COM)
+V2 (+15V)
COM (15V COM)
-V2 (-15V)
ACL (AC Line)
ACN (AC Neutral)
(Ground)
Figure 2.12
— Power Connections