CLS200 Series User’s Guide
Chapter 8: Troubleshooting and Reconfiguring
157
Sixteen-Loop Input Circuit
Sixteen-loop controllers can accept single-ended thermocouple, mVDC, VDC and mA DC inputs.
Unless ordered with special inputs, the controller accepts only signals within the standard range of
-10 to 60mVDC.
To accommodate other signals, the input circuit must be modified. When configured for
thermocouple inputs, 0Ω resistors are installed in all RC locations. To accommodate milliamp current
signals or voltage signals outside the standard range, resistors are added or replaced to scale the
signals to the standard range.
Figure 8.10
shows the schematic for one single-ended sensor input to sixteen-loop controller.
Current Inputs to Sixteen-Loop Controllers on page 157
and
Voltage Inputs to Sixteen-Loop
for specific instructions and resistor values for voltage and current inputs.
IN +
RD
Analog
Input
Terminals
RC
Com
To CLS200
Circuitry
(Voltage only)
(Voltage and Current)
Measurement
Figure 8.10
— Single-Ended Input Circuit in Sixteen-Loop Controllers
Current Inputs to Sixteen-Loop Controllers
Each current input has a 3.0Ω resistor in the RD location for the input.
Table 8.12
—
Resistor Values for Current Inputs to Sixteen-Loop Controllers
INPUT RANGE
RESISTOR VALUE RD
0 to 20mA
3.0Ω
Resistor tolerance: ±0.1%
Table 8.13
—
Resistor Locations for Current Inputs to Sixteen-Loop Controllers
LOOP
RESISTOR LOCATION RD
LOOP
RESISTOR LOCATION RD
1
R42
9
R41
2
R40
10
R39
3
R38
11
R37
4
R36
12
R35
5
R34
13
R33
6
R32
14
R31
7
R30
15
R29
8
R28
16
R27