![Watlow CLS200 Скачать руководство пользователя страница 116](http://html1.mh-extra.com/html/watlow/cls200/cls200_user-manual_3708024116.webp)
CLS200 Series User’s Guide
Chapter 6: Ramp/Soak
116
Features
Ramp/soak in the CLS200 includes the following features:
•
Ready segment sets loop up for profile:
Ready segment can control at setpoint until profile
needs to run. Ready segment events set all available event outputs to desired states before
profile starts.
•
Up to 20 segments per profile:
The controller can store up to 17 profiles, each with up to
20 segments.
•
Multiple profiles run independently:
Each loop can run a different profile or the same profile
can be run independently on more than one loop.
•
Up to two triggers per segment:
Triggers are digital inputs that can be programmed to
start and hold segments based on the trigger’s digital state. You can use any one of the eight
digital inputs for triggers. You can also use the same trigger for more than one segment or
more than one profile.
•
Up to four events per segment:
Digital outputs controlled by the ramp/soak profile. Events
outputs are set at the end of a segment. You can use any of the digital outputs that are not
used for control or for the Serial DAC clock.
•
Tolerance hold ensures time at temperature:
Set a limit on how far the process variable
can vary above or below setpoint. The profile clock only runs when the process variable is
within the limit.
•
Tolerance alarm indicates process not tracking setpoint:
Set a maximum amount of
time for the tolerance hold to wait for a process deviation before notifying the operator. The
operator can acknowledge the alarm and proceed if desired.
•
User-configurable time base:
Program profiles to run for hours and minutes or for minutes
and seconds.
•
Repeatable profiles:
Set any profile to repeat from 1 to 99 times or continuously.
•
Fast setup for similar profiles:
Set up one profile, then copy it and alter it to set up the rest.
•
External reset:
Select a digital input you can use to hold a profile in the “start” state and
restart it.
Table 6.1
summarizes the ramp/soak features of the CLS200.
Table 6.1
—
Ramp/Soak Specifications
Number of possible profiles
17
Number of times to repeat a profile
1 to 99 or or continuous
Number of segments per profile
1 to 20
Number of triggers per segment
Up to 2
Type of triggers
On, On Latched, Off, Off Latched
Number of possible inputs for triggers
8
Number of events per segment
Up to 4
Number of possible outputs for events
(At least one of these outputs must be used for control)
34
Содержание CLS200
Страница 1: ...CLS200 User s Guide...
Страница 193: ...CLS200 Series User s Guide 193 Declaration of Conformity...