![Watlow CLS200 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/watlow/cls200/cls200_user-manual_3708024023.webp)
CLS200 Series User’s Guide
Chapter 2: Installation
23
We recommend you mount the controller in a panel not more than 0.2 in. (5 mm) thick.
1. Choose a panel location free from excessive heat (below 50°C [122°F]), dust, and unauthorized
handling. (Make sure there is adequate clearance for the mounting hardware, terminal blocks,
and cables. The controller extends 7.00 in. (178 mm) behind the panel. Allow adequate room
for wiring and cables beyond the connectors.)
2. Temporarily cover slots in the metal housing so that dirt, metal filings, and pieces of wire do not
enter the housing and lodge in the electronics.
3. Cut a hole in the panel 1.80 in. (46 mm) by 3.63 in. (92 mm) as shown above. (Use caution; the
dimensions given here have 0.02 in. (0.5 mm) tolerances.
4. Remove the brackets and collar from the controller, if they are already in place.
5. Slide the controller into the panel cutout.
6. Slide the mounting collar over the back of the controller, making sure the mounting screw
indentations face toward the back of the controller.
7. Loosen the mounting bracket screws enough to allow for the mounting collar and panel
thickness. Place each mounting bracket into the mounting slots (head of the screw facing
the back of the controller). Push each bracket backward then to the side to secure it to the
controller’s case.
8. Make sure the controller is seated properly. Tighten the installation screws firmly against the
collar to secure the unit. Ensure that the end of the mounting screws fit into the indentations on
the mounting collar.
Mounting the TB50
There are two ways you can mount the TB50: use the pre-installed DIN rail mounting brackets or
use the plastic standoffs. Follow the corresponding procedure to mount the board.
Standoffs
DIN Rail Mount
Figure 2.6
— Mounting the TB50
Содержание CLS200
Страница 1: ...CLS200 User s Guide...
Страница 193: ...CLS200 Series User s Guide 193 Declaration of Conformity...