CLS200 Series User’s Guide
Chapter 4: Setup
91
Selectable values:
NONE
, or any output from
1
to
34
not enabled for closed-loop control or for the
Serial DAC clock.
Deviation Alarm Value
Set the deviation from setpoint at which the high and low deviation alarms occur.
ALARM
01 DEV ALARM
VALUE ? 5
Selectable values:
0
to
255
,
25.5
,
2.55
,
.255
or
.0255
, depending on the
INPUT TYPE
and
DISP FORMAT
settings.
High Deviation Alarm Type
Select an alarm type for the high deviation alarm.
ALARM
01 HI DEV ALARM
TYPE ? OFF
Selectable values:
ALARM
,
CONTROL
or
OFF.
High Deviation Alarm Output Number
Choose a digital output to activate when the high deviation alarm occurs, if desired.
ALARM
01 HI DEV ALARM
OUTPUT ? NONE
Selectable values:
NONE
, or any output from
1
to
34
not enabled for closed-loop control or for the
Serial DAC clock.
Low Deviation Alarm Type
Select an alarm type for the low deviation alarm.
ALARM
01 HI DEV ALARM
TYPE ? OFF
Selectable values:
ALARM
,
CONTROL
or
OFF
.