CLS200 Series User’s Guide
Chapter 6: Ramp/Soak
119
Tolerance Alarm Time
Set a limit on how long the process variable can be outside the tolerance set for the segment before
the tolerance alarm occurs.If the process variable does not return within the tolerance, the tolerance
alarm will recur after the tolerance alarm time elapses again.
If the alarm persists, you may want to reset the profile.
ALARM
A OUT-OF-TOLRNCE
ALARM TIME? 1:00
Selectable values:
0:00
to
99:59
(minutes or hours, depending on the time base setting).
Ready Segment Setpoint
When you assign a profile to a loop, the profile does not start immediately. Instead, it goes to the
ready segment (segment 0) and stays there until you put the profile in run mode.
You can set a setpoint, assign events, and set event states for the ready segment. Use this
parameter to set the ready segment setpoint. Setting the setpoint to
OFF
ensures that control
outputs for the loop running the profile will not come on.
ALARM
A READY SEGMENT
SETPOINT? OFF
Selectable values:
-999 to 9999, or
OFF
. See
Setpoints and Tolerances for Various Input Types on
Ready Segment Edit Events
Press
YES
to set or edit the ready state for all outputs that are not used for control or for the Serial
DAC clock. When you assign a profile, the controller starts the ready segment: it goes to the setpoint
and puts all the outputs in the state you set here. The outputs stay in the states they are set to until
their states are changed at the end of subsequent segments.
ALARM
A READY SEGMENT
EDIT EVENTS ?
Press
NO
to advance to
EXTERNAL RESET INPUT NUMBER
.