CLS200 Series User’s Guide
Chapter 6: Ramp/Soak
124
Last Segment
Specify whether the current segment is the last one in the profile.
ALARM
A SEGMENT 01
LAST SEGMENT? NO
Selectable values:
NO
or
YES
.
Repeat Cycles
Set the number of times you want a profile to repeat or cycle.
The profile returns to
START
mode after completing the number of cycles specified here.
ALARM
A REPEAT CYCLES
? 1
Selectable values:
1
to
99
, or
C
(continuous cycling).
Setpoints and Tolerances for Various Input Types
Setpoints and tolerances are set in segments before the profile is assigned to a particular loop.
When the profile is used with a loop, the
INPUT TYPE
and
DISP FORMATS
settings are applied to
the following parameters:
• Ready setpoint
• Segment setpoint
• Segment tolerance
Refer to
Table 6.3
to determine how these parameters are affected for the various
INPUT TYPE
and
DISP FORMAT
settings.
Table 6.3
—
Display Formats
INPUT TYPE
DISPLAY FORMAT
YOU ENTER IN
THE PROFILE
RESULTING VALUE WHEN PROFILE IS
ASSIGNED TO A LOOP
Thermocouples
and RTDs
N/A
300
300.0
Linear
-999 to 3000
300
300.0
-9999 to 30000
300
300.0
-999.9 to 3000.0
300
300.0
-99.99 to 300.0
300
30.00
-9.999 to 30.000
300
3.000
-9999 to 3.0000
300
0.3000