CLS200 Series User’s Guide
Chapter 10: Specifications
168
Table 10.14
—
RTD Range and Resolution
NAME
RANGE
IN °F
RANGE
IN °C
RESOLUTION
IN °C
MEASUREMENT
TEMPERATURE
IN °C
ACCURACY* AT
25°C AMBIENT
ACCURACY* AT
0 TO 50°C
AMBIENT
°F
°C
°F
°C
RTD1
-148.0 to
527.0
-100.0 to
275.0
0.023
25
±0.7
±0.4
±1.0
±0.6
275
±1.9
±1.1
±2.8
±1.6
RTD2
-184 to
1544
-120 to
840
0.023
25
±2.5
±1.4
±5.9
±3.3
840
±2.9
±1.6
±8.6
±4.8
Table 10.15
—
Input Resistance for Voltage Inputs
RANGE
INPUT RESISTANCE
0 to 10V
50kΩ
0 to 5V
40kΩ
Table 10.16
—
Digital Inputs
PARAMETER
DESCRIPTION
Number
8
Configuration
8 selectable for output override, remote job
selection
Input Voltage Protection
Diodes to supply and common. Source must limit
current to 10mA for override conditions
Voltage Levels
<1.3V: Low
>3.7V: High (TTL)
5V maximum, 0V minimum
Maximum Switch Resistance to
Pull Input Low
1kΩ
Minimum Switch Off Resistance
11kΩ
Update Rate
6Hz
Outputs
The controller directly accommodates switched dc and open-collector outputs only. These outputs
can be used to control a wide variety of loads. They are typically used to control SSRs or other
power switching devices which in turn control, for example, heaters. They may also be used to
signal another device of an alarm condition in the controller.
An open-collector CPU watchdog output is also provided so that an external device may monitor the
CPU state.