CLS200 Series User’s Guide
Chapter 6: Ramp/Soak
120
Ready Event Output
Press
NO
to increment the output number. Press
YES
to set the event state to
ON
or
OFF
.
This parameter appears only if you answered
YES
to
READY SEGMENT EDIT EVENTS?
ALARM
A READY EVENT
OUTPUT 15? OFF
Selectable values:
ON
or
OFF
.
When you are done, press
BACK
to return to
READY SEGMENT EDIT EVENTS
, then press
NO
to
go to the next parameter.
External Reset Input Number
Select one of the eight digital inputs as an external reset. When the reset input is on, the profile is set
to
RUN
mode at the beginning of the first segment. As long as the reset input is on, the profile is held
at the beginning of the first segment. Once the reset input turns off the profile begins to run.
ALARM
A EXTERNAL RESET
INPUT NUMBER? N
Selectable values:
1
to
8
, or
N
(for no external reset).
Edit Segment Number
Each profile is made up of several segments (up to 20). Choose the segment to edit.
ALARM
A EDIT SEGMENT
NUMBER? 15
Selectable values:
1
to
20
.
The first time you use this parameter, it defaults to segment 1. When you finish editing a segment,
the controller goes to the next segment. This loop continues until you make a segment the last
segment of a profile.
Segment Time
Enter the duration of the segment.
ALARM
A SEGMENT 11
SEG TIME? 000:00
Selectable values:
0:00
to
999:59
(hours and minutes or minutes and seconds, depending on
the selected time base).