- (CS01 - 15) -
Control system
- (CS01 - 15) -
C
O
N
T
R
O
L
SY
S
T
E
M
C
O
N
T
R
O
L
SY
S
T
E
M
LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
OR DISPLAY
FACTORY
SETTING
1620
I
Release of DHW load
24h / day
Heating circuit time programme
Programme 4 / DHW
Off-peak tariff (Off-peak)
Programme 4 / DHW
and Off-peak
Programme
4 / DHW
24h / day
: The temperature of the DHW is constantly maintained at the DHW comfort
setting.
Heating circuit time programme
: The DHW is produced according to the programming
for the ambient temperature (with 1 hour in advance when switched on).
Programme 4 / DHW
: The DHW programme is separate form the heating circuit
programme.
Off-peak tariff*
: The electrical backup heating is only authorised to operate during the
off-peak period.
T'prog 4/DHW or low-tariff *
: The electrical backup heating is authorised to operate
during the comfort period or off peak.
* - Connect the "Power Provider" contact to input EX2. In the case of a day /night contract,
the electric back-ups for the DHW tank are subject to the power supplier's tariffs. Switching
on the electric back-up for the DHW tank is only authorised during off-peak hours.
1640
I
Legionella function
Off, Periodically (depending line
setting 1641), Fixed weekday
(depending line setting 1642)
Off
1641
I
Legionella function periodically
1 to 7
7
1642
S
Legionella function weekday
Monday, Tuesday,...
Saturday
1644
S
Legionella function time
1645
S
Legionella funct setpoint
1646
S
Legionella funct duration
1647
S
Legionella funct circ pump
Off, On
Off
1660
S
Legionella function weekday
Time program 3/HCP,
DHW release,
Time program 4/DHW,
Time program 5
DHW release
Swimming pool (Only with swimming pool kit option)
2055
U
Setpoint solar heating
8... 80 °C
26°C
2056
U
Setpoint source heating
8... 35 °C
22°C
2057
S
Swi diff source heating
0.5... 3 °C
0.5°C
2065
S
Charging priority solar
Priority 1, Priority 2,
Priority 3
Priority 1
2080
S
Setpoint source heating
No, Yes
Yes
Heat pump
2803
S
Overrun time cond pump
8…240s
240s
2843
S
Compressor off time min
0…120min
8min
2844
S
Switch-off temp max
8…100°C
75°C
2862
S
Locking time stage 2 / mod
0…40min
5min
2873
S
Compressor mod run time
10…600s
240s
2882
S
Release integral electric flow
0…500°Cmin
100°Cmin
2884
S
Release electric flow below OT
Electrical release - start-up with
outside temperature
-30…30°C
2°C
2916
S
Max setpoint HP DHW charg
8… 80°C
58°C