- (CS01 - 19) -
Control system
- (CS01 - 19) -
C
O
N
T
R
O
L
SY
S
T
E
M
C
O
N
T
R
O
L
SY
S
T
E
M
LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
OR DISPLAY
FACTORY
SETTING
8007
I
State solar
---
8010
I
State buffer
---
8011
I
State swimming pool
---
8022
I
State supplementary source
---
8025
I
State cooling circuit 2
---
Generator diagnosis
8400
I
Compressor 1
Off, On
Off
8402
I
Electrical resistance flow 1
Off, On
Off
8403
I
Electrical resistance flow 2
Off, On
Off
8406
I
Condenser pump
Off, On
Off
8407
S
Speed condenser pump
0…100%
---
8410
U
Return temp HP
0... 140 °C
---
Setpoint (flow) HP
0... 140 °C
---
8412
U
Flow temp HP
0... 140 °C
---
Setpoint (flow) HP
0... 140 °C
---
8413
U
Compressor modulation
0…100%
---
8414
I
Modulation electric flow
0…100%
---
8425
S
Temp differential condenser
-50…140°C
---
8450
S
Hours run compressor 1
00:00
---
8454
S
Locking time Heat Pump
Reset ? (no, yes)
0…2730h
---
8455
S
Counter number of locks HP
Reset ? (no, yes)
0…65535
---
8456
S
Hours run electric flow
Reset ? (no, yes)
0…2730h
---
8457
S
Start counter electric flow
Reset ? (no, yes)
0…65535
---
8458
I
State smart grid
Draw disabled
Draw free
Draw wish
Draw forced
Draw free
8460
I
Heat pump throughput
0... 65535 l/min
---
Diagnostics consumers
8700
U
Outside temp
-50…50°C
---
8701
U
Outside temp min
Reset ? (no, yes)
-50…50°C
50°C
8702
U
Outside temp max
Reset ? (no, yes)
-50…50°C
-50°C
8703
I
Outside temp attenuated
Reset ? (no, yes)
-50…50°C
---
This is the average of the outside temperature over a 24-hour period.
This value is used for automatic Summer / Winter switchover (line 730).
8704
I
Outside temp composite
-50…50°C
---
The mixed outside temperature is a combination of the current outside temperature and the
average outside temperature calculated by the regulator. This value is used for calculating
the initial temperature.
8730
I
Heating circuit pump, circuit 1
Off, On
Off
8731
I
Mixer valve HC1 open
Off, On
Off
8732
I
Mixer valve HC1 closed
Off, On
Off
8740
U
Room temp 1
0... 50 °C
---
Room setting 1
20°C