Time program functions (Heating circuit 1 & 2, DHW, Cooling)
z
Several control programs are available for the
heating circuits and the production of DHW. They
are initiated in "Automatic" mode and control the
change in temperature levels (and therefore the
associated setpoints, reduced and comfort) via the
adjusted changeover times.
Enter changeover times:
Changeover times can be adjusted in a combined
way, i.e., identical times for several days or distinct
times for certain days. Preselecting groups of days
(e.g., Mon...Fri and Sat...Sun) having the same
changeover times make adjustment of the
changeover program considerably shorter.
Changeover Points
LINE
FUNCTION
HC1
HC2
4/DHW
5
500
520
560
600
Preselection
(Mo-Su / Mo-Fr / Sa – Su / Mo...Su)
501
521
561
601
1
st
phase on
502
522
562
602
1
st
phase off
503
523
563
603
2
nd
phase on
504
524
564
604
2
nd
phase off
505
525
565
605
3
rd
phase on
506
526
566
606
3
rd
phase off
Standard Program
LINE
FUNCTION
516, 536, 576, 616
Default values
(No /Yes)
All time programs can be reset to factory settings.
Each time program has its own programming line
for this reset action.
In this case, individual settings will be lost!
Holidays
LINE
FUNCTION
HC1
HC2
641
651
Preselection
642
652
Period start (Day / Month)
643
653
Period end (Day / Month)
648
658
Operation level
The holiday program enables changing the heating
circuits over to a selected operating level according
to the date (calendar).
Important:
The holiday program can be used only in the
automatic mode.