Safety/Limit
thermostat
intervention
Boiler does not
work, ALL 07
error code
flashing on the
screen
Water
overtemperature
(T>95°C)
> Lack of water on the
system
> Pump blockage
> Pump failiure
> Pump harness
> Installation blockage
1-) RESET boiler at first check if problem removed
2-) Check boiler central heating valves are open if they are closed
open of all
3-) Check all radiator valves are open if they are closed open of all
minimum 3 meters of radiator must be open
4-) RESET boiler and check if problem removed
5-) Call for authorised service at first
6-) Check Pump operation if the pump circuation through the heat
exchanger is enough
7-) Check intermittent contacts on harness carefully specially Pump
and PWM cable and speciallypump main supply connector and
specially pump main connector, measure voltage from connectors
8-) Check if there is air on the heat exchanger or system, remove air.
9-) Check heat exchanger water path againts clogging
10-) Installation water path againts clogging
11-) Reset & Restart boiler
ALL 08
Flame circuit
failure / Flame
detection error
If the flame control
section recocnises
the presence of a
flames in pahases
when they should
not be present, it
means that there is a
breakdown in flame
detection circuit
> Aging or rust on the
electrode
> Electrode position
> Cabeling
disconnections
> Water blokage on
syphon
> Electronic board
1-) Call for authorised service at first
2-) Check any problems on the ionisation electrode, (like
condensation, rust etc.), and control poistioning of the electrode.
3-) Check for condensation on the cabling AND/OR on board
4-) Check earth connection between board and electrode
5-) Check electrode cabeling between board and electrode
6-) Check syphone against water blokage
7-) If fault still persists Replace board but do not forget to record the
default parameter values. Adjust P1 releated to the default value of
boiler power.
E 09
No water
circulation in the
system
Boiler does not
work, ALL 09 error
code flashing on
the screen Flow
temperature sensor
has detected a
temperature rise in
excess of 5°C/sec
> Lack of water on the
system
> Pump blockage
> Pump failiure
> Pump harness
> Installation blockage
1-) RESET boiler at first check if problem removed
2-) Check boiler central heating valves are open if they are closed
open of all
3-) Check all radiator valves are open if they are closed open of all
minimum 3 meters of radiator must be open
4-) RESET boiler and check if problem removed
5-) Call for authorised service at first
6-) Check Pump operation if the pump circuation through the heat
exchanger is enough
7-) Check intermittent contacts on harness carefully specially Pump
and PWM cable and speciallypump main supply connector and
specially pump main connector, measure voltage from connectors
8-) Check if there is air on the heat exchanger or system, remove air.
9-) Check heat exchanger water path againts clogging
10-) Installation water path againts clogging
11-) Reset & Restart boiler
ALL 10
Plant Probe
OR
AUX Probe
temperature
sensor faulty
Boiler does not
work, ALL 10
error code
flashing on the
screen
> Plant probe OR AUX
Probe temperature
sensor faulty
> Plant Probe OR AUX
sensor is open or short
circuit
1-) Call for authorised service at first
2-) Check intermittent contacts or open contacts on harness
carefully
3-) Temperature sensor ressistance according to page XXX at
section XXX if its out of tolerance replace NTC
4-) Check cabeling and connectors between double NTC and board
5-) Reset & Restart boiler
ALL 13
Exhaust
temperature
probe
overtemperature
alarm
Boiler does not
work, ALL 13
error code
flashing on the
screen
> Over temperature flue
gas outlet value
> P80 value C°
1-) Call for authorised service at first
2-) Check Pump operation if the pump circuation through the heat
exchanger is enough
3-) Check intermittent contacts on harness carefully specially Pump
and PWM cable
4-) Check if there is air on the heat exchanger, remove air
5-) Check heat exchanger water path againts clogging
6-) Installation water path againts clogging
7-) Reset & Restart boiler
ALL 14
Exhaust ( FLUE )
temperature
probe fault
Boiler does not
work, ALL 14
error code
flashing on the
screen
> Central heating FLUE
temperature sensor
faulty
> Probe is open or short
circuited
1-) Call for authorised service at first
2-) Check intermittent contacts or open contacts on harness
carefully
3-) Check FLUE temperature sensor ressistance according to page
XXX at section XXX if its out of tolerance replace NTC
3-) Check cabeling and connectors between FLUE NTC and board
4-) Reset & Restart boiler
ALL 15
Fan failure
(feedback/supply)
Boiler does not
work, ALL 15
error code
flashing on the
screen
> Fan harness
1-) Call for authorised service at first
2-) Check intermittent contacts or open contacts on harness
carefully on fan main supply, if main supply not connected then fan
will not operate and boiler will not ignite
3-) Check intermittent contacts or open contacts on harness
carefully on fan PWM connection, if PWM connection not connected
then fan will work at %100 capacity
4-) Reset & Restart boiler