3.7. TRANSPARENT PARAMETERS MENU (TSP)
Parame-
ter no.
Parameter
Type of
Parameter
Value Field
Viwa 90
Default
Viwa 115
Default
Viwa 125
Default
Viwa 150
Default
Par 01
Quick configuration for combustion and power
1 = 90 kw
2 = 115 kw
3 = 125 kw
4 = 150 kw
INSTALLER
" - - " / 1 – 53
1
2
3
4
Par 02
Quick configuration for hydraulic configuration of the
boiler and plant parameters
INSTALLER
1 – 14
5
5
5
5
Par 03
Digital Input CN 11 - Pin 4 configuration
INSTALLER
1 – 3
1
1
1
1
Par 04
Water pressure sensor configuration
0 = Not used
1 = Not used
2 = Water pressure sensor: 0,8 - 5,7 Bars With high
pressure alarm
INSTALLER
0 – 2
2
2
2
2
Par 05
AUX Relay configuration
1 = Alarm relay out put - Normally open
2 = Recirculation pump
3 = Water filling
4 = Alarm relay out put - Normally closed
5 = Heat pump
6 = Zone valve 2
INSTALLER
1 – 6
6
6
6
6
Par 06
Not USED
INSTALLER
0 – 1
1
1
1
1
Par 07
Outside Temperature Sensor (Master) / Plant Sensor
(Slave) Beta Value
0 = 3435
1 = 3977
INSTALLER
0 – 2
0
0
0
0
Par 08
Ignition fan speed ( Par 08 x100) rpm
INSTALLER
"9,9 - 81
( 0,3 each step )"
33 = NG
33 = NG
33 = NG
33 = NG
Par 09
Percentage increase in fan speeds to be used in case
of clapet ( % )
INSTALLER
0 % - 40 %
0
0
0
0
Par 10
DHW Priority
0 = Paralel operation ( DHW and CH operates paralel
)
1 = DHW Priority ( if there is DHW request first
priority is DHW )
INSTALLER
0 – 1
0
0
0
0
Par 11
External temperature sensor correction ( C° )
INSTALLER
- 5 C°…..+ 5 C°
0
0
0
0
Par 12
Not USED
INSTALLER
" - - " / 0 – 199
3
3
3
3
Par 13
Modulating pump configuration (if PWM connected
to boiler )
" - - " = No modulation
AU = Automatic modulation in range of %30 - %100
INSTALLER
" "" - - ""
AU / 30 – 100 "
AU
AU
AU
AU
Par 14
Second TA low voltage configuration
" - - " = Contact TA 2
5…160 = 0 - 10 V - DC.
INSTALLER
" - - " / 5 – 160
" - - "
" - - "
" - - "
" - - "
Par 15
Cascade adress
" - - " = No cascade - Single boiler
00 = Master boiler
01…07 = Slave boiler
INSTALLER
" - - " / 00 – 07
" - - "
" - - "
" - - "
" - - "
Par 16
DHW Sensor Beta Value
0 = 3435
1 = 3977
INSTALLER
0 – 2
1
1
1
1
Par 18
Post ventilation time ( sec x 10 )
INSTALLER
1 - 180
30
30
30
30
Par 19
Configutation of plant type
0 = 2 Heating zone ( 2 Zon )
1 = 3 Heating zone ( 3 Zon )
INSTALLER
0 – 1
0
0
0
0
Par 20
Minimum set temperature for zone 1 heating ( C° )
INSTALLER
Par 64 OEM…
Par 21 Installer
20
20
20
20
Par 21
Maximum set temperature for zone 1 heating ( C° )
INSTALLER
Par 20 Installer
...Par 65 OEM
80
80
80
80
Par 22
Climatic regulation for zone 1
INSTALLER
03 – 40
20
20
20
20
Par 23
Minimum set temperature for zone 2 heating ( C° )
INSTALLER
Par 64 OEM…
Par 24 Installer
20
20
20
20
Par 24
Maximum set temperature for zone 2 heating ( C° )
INSTALLER
Par 23 Installer
...Par 65 OEM
80
80
80
80