Parame-
ter no.
Parameter
Type of
Parameter
Value Field
Viwa 90
Default
Viwa 115
Default
Viwa 125
Default
Viwa 150
Default
Par 25
Climatic regulation for zone 2
INSTALLER
03 – 40
20
20
20
20
Par 29
Delta temperature CH flow and return for pump
modulation
( incase Par 13 set to AU )
INSTALLER
10 – 40
20
20
20
20
Par 30
Post circulation time ( sec )
INSTALLER
0 – 199
60
60
60
60
Par 31
Maximum CH power ( % )
INSTALLER
% 0 – %100
100
100
100
100
Par 32
Delay time to activate Zone 1 pump ( sec x 10 )
INSTALLER
0 – 199
1
1
1
1
Par 33
Delay time for ignition ( min )
INSTALLER
0 - 10 min (dak)
3
3
3
3
Par 34
Not USED
INSTALLER
0 – 100
0
0
0
0
Par 35
Antifreezing activation temperature ( C° )
INSTALLER
0 C°... +20 C°
5
5
5
5
Par 36
Antifreezing activation external temperature ( C° )
INSTALLER
(-5 C°)….+5 C°
-2
-2
-2
-2
Par 37
Not USED
INSTALLER
- - / 00 – 100
100
100
100
100
Par 38
Post circulation time DHW ( sec )
INSTALLER
0 – 199
20
20
20
20
Par 39
Anti Legionella function
0 = Disable
1 = Enable
INSTALLER
0 – 1
1
1
1
1
Par 40
Not USED
INSTALLER
0 – 3
0
0
0
0
Par 41
Not USED
INSTALLER
0 – 199
12
12
12
12
Par 42
Not USED
INSTALLER
0 – 1
1
1
1
1
Par 44
Not USED
INSTALLER
1 – 8
1
1
1
1
Par 45
Not USED
INSTALLER
5 – 50
8
8
8
8
Par 46
Not USED
INSTALLER
" - - " / 0 – 199
0
0
0
0
Par 47
Not USED
INSTALLER
" - - " / (-30 C°) ... 0 C°
-10
-10
-10
-10
Par 48
Not USED
INSTALLER
" - - " / 80 – 199
120
120
120
120
Par 49
Reset INSTALLER TSP parameter values to default
Note: Par 1 to -- and Par 2 a -
" - - " = No reset
1 = all values Par 1 to Par 48 reset to the default
values
INSTALLER
" - - " / 1
" - - "
" - - "
" - - "
" - - "
Par 50
Water filling
0 = Disable
1 = Enable
OEM
0 – 1
0
0
0
0
Par 51
Selection Flow siwtch / flow meter
0 = Flow switch
1 = Flow meter
OEM
0
0
0
0
0
Par 52
AUX sensor configuration
0 = Not used
1 = Pre heat sensor
2 = Tank sensor ( DHW )
3 = No-Frost sensor
4 = Tank thermostad
5 = Plant probe
OEM
0 – 5
4
4
4
4
Par 53
Not USED
OEM
0 – 1
0
0
0
0
Par 54
Configuration of 3 way valve
0 = Not used
1 = 2 pump
2 = 3-way electric ( 230 VAC )
OEM
0 – 2
2
2
2
2
Par 55
Not USED
OEM
0 – 1
0
0
0
0
Par 57
Main supply frequency
50 = 50 Hz
60 = 60 Hz
OEM
50 / 60
50
50
50
50
Par 58
Not USED
OEM
10 – 199
100
100
100
100
Par 59
Flue gas sensor configuration
0 = No
1 = Yes
OEM
0 – 1
1
1
1
1
Par 60
Fluxmeter value for DHW request activation ( Value =
liter / minute)
OEM
1 - 4 lt/min
(0,1 per step )
2,5
2,5
2,5
2,5
Par 61
Tank derivatives value
OEM
0 …. - 5
( C° / min )
0
0
0
0
Par 62
DHW Maximum temperature ( C° )
OEM
30 C° – 80 C°
60
60
60
60