Connections, operating elements and LEDs
Subject to errors and modifications:
input group have the same ground reference. For signals with
with a different reference ground, the circuit should be
configured in separate input groups as shown in the example.
The cables should not be longer than necessary. Unshielded
cables can be used for lengths under 2m.
Longer runs should always use appropriate shielding measures to
protect against noise. We recommend using shielded cable and/or
ferrite cores as well as separate cable runs to prevent noise
signals from being interpreted as actual signals.
In addition to detecting the input status (ON/OFF), each input also
has a counter. As shipped the edges are counted (state change).
The counters in the first input group can alternately be changed
from edge to pulse counting.
3.6.2 Output circuit
The 12 outputs of the Web-IO are current sourcing. The supply
voltage for the outputs can be b6 V and +30 V and is
brought in through terminals 16 (Vdd) and 15 (GND).
on
error
system error
http:// . . . /diag
0
11
10
9
GND 8
7
5
4
6
3
2
1
GND
GND
GND
INPUT GROUP 0
INPUT GROUP 1
INPUT GROUP 2
0
11
10
9
GND
8
7
5
4
6
3
2
1
Vcc
6-30V DC
+Vdd
OUTPUT GROUP 0
OUTPUT GROUP 1
OUTPUT GROUP 2
12-24V
Vcc
W&T
www.wut.de
Web-IO
#57630
12xDigital-IO <-> 10/100BT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26
28 29 30 31 32
27
Reset
Power
St
atus
Error
Serial Port
Vcc
Vdd
+Vcc
Intern
- Vcc
Intern
~
~
principle diagram
DC
DC
+
-
~
~
Example of an output circuit