51
W&T
Access types
Subject to errors and modifications:
5.2
Specifying the output mode
As already described, you must specify in which mode each in-
dividual output is supposed to work. The corresponding
configuration can be made under
Config >> Device >> Output
Mode
.
m
Required access rights:
Administrator
Output Mode
Here the mode used for each output is specified. The factory
default is for all ports HTTP. Please note that in most modes a
few additional settings besides output mode need to be made,
such as enabling of the mode. For more detailed information,
refer to the description of the respective operating mode.
Safety Timeout
If no network activity is detected for the timeout period set here,
the Web-IO sets the outputs to a configurable output pattern.
Which outputs should be involved and what their status should
be is configured under
Config >> Ports >> Outputs
. A detailed
description of the safety timeout and safety state can be found
in the section
Safety State / Timeout
.
Load Control:
By activating this option you are enabling load monitoring. Load
monitoring applies to all outputs.
After selecting the output modes, click on Temporary Storage to
send the settings to the Web-IO. To activate, use the
Logout
button
and click on
Save.