84
W&T
Controlling the Web-IO with TCP/UDP Sockets
So that under UDP a message can be automatically received
when states change, the Web-IO provides a variety of various
alarm conditions.
i
A detailed description of how to use these alarm
possibilities can be found in the
Alarms
section
Include a header
The Web-IO can if needed precede the sent string with a header
containing the IP address and the name.
To enable a header, go to
Config >> Basic Settings >> HTTP
and
select
GET Header enable
. Clicking on
Logout
and
Save
activates sending of the header.
Example:
.
The IP address of the Web-IO is 172.16.232.17.
.
„W&T Web-IO 12xDigital“ was entered as the device name
under
Config >> Device >> Text
„“.
.
GET /input?PW=&
was used by the application to poll the
inputs.
The Web-IO returns:
172.16.232.6;W&T Web-IO 12xDigital;input;0000
If GET Header enable was activated, the header precedes all data
sent by the Web-IO.
Содержание 57630
Страница 8: ...8 W T Content...
Страница 22: ...22 W T Assigning the IP address...
Страница 44: ...44 W T configuring the network parameters...
Страница 194: ...194 W T Diacnostics and testing...
Страница 211: ...211 W T Decalration of conformity Subject to errors and modifications 7 9 Declaration of Conformity...