198 •
I/O Modules
Configuration and Parameter Setting of the Modules
WAGO-I/O-SYSTEM
750
PROFINET IO
Parameter
Value
Significance
Default value behavior of the
outputs
Applies when the I/O controller does not supply
valid output data for the module or the group of
modules
according to the device settings*)
•
the set strategy on the side of the station
distributor applies (I/O device).
Outputs are set to 0
•
so that all outputs are immediately reset
Outputs maintain the last valid value
•
that all outputs maintain the last valid value
outputs take on their default value
•
so that all outputs switch to their configured
default value
Asynchronous diagnostics
message
Channel x (x = 0, 1)2)
The following occurs per diagnostics data sets and
diagnostics alarm with external faults
locked*)
•
not transferred to the I/O Controller
released
•
transferred to the I/O Controller
Process data format channel x
The process data will be transferred
(x = 0.1)
according to the device settings*)
•
using the format settings of the I/O device.
INTEL (LSB-MSB)
•
Little Endian Format
MOTOROLA (MSB-LSB)
•
Big Endian Format
Substitute output data channel x
(x = 0.1)
0x0000
*)
– 0x7FFF
or
0x0000
*)
– 0xFFFF
If the switching of substitute values has been
selected as a fault strategy, the substitute output
data of the individual output channels can be
determined here.
*) Default settings
2)
Existence module dependant