PROFINET IO 750-340
•
51
I/O Device Configuration
WAGO-I/O-SYSTEM 750
PROFINET IO
Module
Description
Name example
DO_DIA_32
Configuration module for 32 digital input
and outputs, 4 bytes are reserved in the
output and output process image of the I/O
controller. The bit information in the first
byte of the output area is allocated to the
output data of the configured I/O module
according to the number of existing signal
channels. The bit information in the first
byte of the input area is allocated to the raw
diagnostics data of the individual signal
channels. Remaining bit locations of the
reserved input and output area (indicated in
brackets with a positive sign) can be
allocated to the signal conditions of the
following digital I/O modules having the
same type of signal. This is done by
configuring the
Dx0
or
Dx_DIA_0
modules
of the relevant I/O modules.
750-507 2DA(+30 BIT I/O),
DIA in E-PA
DO_DIA_16
Configuration module for 16 digital input
and outputs, 2 bytes are reserved in the
output and output process image of the I/O
controller. The bit information in the first
byte of the output area is allocated to the
output data of the configured I/O module
according to the number of existing signal
channels. The bit information in the first
byte of the input area is allocated to the raw
diagnostics data of the individual signal
channels. Remaining bit locations of the
reserved input and output area (indicated in
brackets with a positive sign) can be
allocated to the signal conditions of the
following digital I/O modules having the
same type of signal. This is done by
configuring the
Dx0
or
Dx_DIA_0
modules
of the relevant I/O modules.
750-507 2DA(+12 BIT A),
DIA in E-PA
DO_DIA_8
Configuration module for 8 digital input
and outputs, 1 byte is reserved in the output
and output process image of the I/O
controller. The bit information of the output
area is allocated to the output data of the
configured I/O module according to the
number of existing signal channels. The bit
information of the input area is allocated to
the raw diagnostics data of the individual
signal channels. Remaining bit locations of
the reserved input and output area
(indicated in brackets with a positive sign)
can be allocated to the signal conditions of
the following digital I/O modules having
the same type of signal. This is done by
configuring the
Dx0
or
Dx_DIA_0
modules
of the relevant I/O modules.
750-507 2DA(+4 BIT A),
DIA in E-PA