214 •
I/O Modules
Configuration and Parameter Setting of the Modules
WAGO-I/O-SYSTEM
750
PROFINET IO
F-Parameter
Value
Significance
F_Check_iPar
Manufacturer specific i-parameters can be found
within the F-parameters that
NoCheck
1)
•
not requested for inspection
Check
•
requested for inspection
F_SIL
The safety catagory reached is
SIL3
1)
SIL
3
F_CRC_Length
The length of the CRC for backing up the process
data is
3-Byte-CRC
1)
3
Byte
F_Par_Version
The version of the F Parameter set is
1
1)
1 = V2-Mode
F_Source_Add
PROFIsafe address of the F-Host
1
…65534
F_Dest_Add
PROFIsafe address of the I/O module (F-Slave)
1
…1022
F_WD_Time
Monitoring time of the F Data set in ms
50 ... 100
*)
... 10000
*) Default settings
1)
settings that cannot be modified