I/O Modules • 183
Configuration and Parameter Setting of the Modules
WAGO-I/O-SYSTEM 750
PROFINET IO
5.3.2.7
8-Channel Digital Output Modules with 1 Bit Diagnostics Status per
Channel
Instances
PNIO
Module type
EA Type
Module type member
PNIO-Data
type
Input
Output
8DA
DO_8
- 1
8DA,
DIA in E-PA
DO_DIA_8
Unsigned 8-
Bit field
1 1
8DA(+8 BIT O)
DO_16
- 1
8DA(+8 BIT I/O),
DIA in E-PA
DO_DIA_16
Unsigned
16-Bit field
1 1
8DA(+24 BIT O)
DO_32
- 1
8DA(+24 BIT I/O),
DIA in E-PA
DO_DIA_32
75x-537
Unsigned
32-bit field
1 1
* 8DA(-8 BIT A)
DO_0
* 8DA(-8 BIT I/O),
DIA in E-PA
DO_DIA_0
75x-537*
- -
-
Inputs
Bit allocation
PNIO
Module type
Length
[Bit]
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Note
A7
A6
A5
A4
A3
A2
A1
A0
\ - - - - - - - - - - - - - - Output - - - - - - - - - - - - - - /
8DA
8DA(+8 BIT O)
8DA(+24 BIT O)
8
8, 16 or 32 bits are applied in the output
process image of the station proxy (fieldbus
coupler) by fitting a slot with these modules..
The bits 2
0
and 2
7
are assigned with the
signal condition of the physically connected
I/O module. The bits 2
8
to 2
15
or 2
31
marked
green are made available for the output and /
or confirmation information of the following
modules. One byte process data qualifier
(IOCS) is managed in the transmission
direction of the I/O controller in the cyclic
PROFINET IO telegram for these modules.
A7
A6
A5
A4
A3
A2
A1
A0
8
\ - - - - - - - - - - - - - - Output - - - - - - - - - - - - - - /
D7
D6
D5
D4
D3
D2
D1
D0
\ - - - - - - - - - - - - - - Input - - - - - - - - - - - - - - /
8DA(+8 BIT I/O),
DIA in E-PA
8DA(+8 BIT I/O),
DIA in E-PA
8DA(+24 BIT I/O),
DIA in E-PA
8
8, 16 or 32 bits are applied in the input and
output process image of the station proxy
(fieldbus coupler) by fitting a slot with these
modules. The bits 2
0
and 2
7
in the output area
are assigned with the signal condition of the
physically connected I/O module. The bits 2
8
to 2
15
or 2
31
marked green are made available
for the output and / or confirmation
information of the following modules. The
bits 2
0
and 2
7
in the input area are assigned
with the diagnostics condition of the
physically connected I/O module. The bits
marked green are made available for the
input and / or diagnostics information of the
following module slots. Two byte process
data qualifiers (IOCS, IOPS) are managed in
the transmission direction of the I/O
controller in the cyclic PROFINET IO
telegram for these modules.