PROFINET IO 750-340
•
101
LED Indication
WAGO-I/O-SYSTEM 750
PROFINET IO
9
Buscontroller initialization error Switch off the supply voltage of
the node, replace the buscoupler
and switch on again.
10
Buffer power failure real time
clock (RTC)
Set the clock and hold up the
power supply of the buscoupler for
at least 15 minutes in order to
charge the Goldcap.
11
Fault during read access to the
real time clock (RTC)
Set the clock and hold up the
power supply of the buscoupler for
at least 15 minutes in order to
charge the Goldcap.
12
Fault during write access to the
real time clock (RTC)
Set the clock and hold up the
power supply of the buscoupler for
at least 15 minutes in order to
charge the Goldcap.
13
Clock interrupt fault
Set the clock and hold up the
power supply of the buscoupler for
at least 15 minutes in order to
charge the Goldcap.
14
Maximum number of gateway
modules or mailbox modules
exceeded.
Reduce the number of
correspondent modules to a valid
number.