PROFINET IO 750-340
•
59
I/O Device Configuration
WAGO-I/O-SYSTEM 750
PROFINET IO
3.1.3.3.3
Fault Safe Module Parameters (F-Parameters)
Fault safe I/O modules require the standardized PROFIsafe configuration to
ensure a safe exchange of productive data.
Parameter
Setting
Description
F_Check_iPar
NoCheck
*1)
There are no individual parameters
contained in the F-parameters that
have to be checked.
F_SIL
SIL3
*1)
The module complies with the safety
catagory 3.
F_CRC_Length
3-Byte-CRC
*1)
The productive data transfer is
safeguarded using a 3 byte CRC in
case of PROFINET IO.
F_Par_Version
1
*1)
all outputs maintain the last valid
value
F_Source_Add
1 ... 65534
The F-Source address addresses the
F-Host
F_Dest_Add
1 ... 1022
The F-Target address addresses the
F-Device
F_WD_Time
100
*2)
1 ... 10000
The F-Watchdog monitors the data
exchange between the F-Host and F-
Device. The settings are carried out
in milliseconds.