54
•
PROFINET IO 750-340
I/O Device Configuration
WAGO-I/O-SYSTEM
750
PROFINET IO
Module
Description
Marking
SSI_EM
Configuration module the SSI interface. A
structure of 1 byte control and 1 double
word (4 bytes) of data are provided in the
output process image of the I/O controller.
A structure of 1 byte status and 1 double
word (4 bytes) of data are provided in the
input process image of the I/O controller.
The status byte supplies the information for
the upcoming faults in the productive data
exchange. The productive dada exchange
does not have any significance in the output
area of the I/O module.
750-630 1SSI, EM
3.1.3.2.4 Configuring System Modules
Five configuration modules are available for the diagnostic capable field side
supply modules. Four of these modules provide the diagnostics information in
the input process image.
Module
Description
Exemplary name
PE_DIA_32
Configuration module for 32 digital inputs,
4 bytes are reserved in the input process
image of the I/O controller. The bit
information in the first byte is allocated to
the 2 bit diagnostics data of the configured
supply module. Remaining bit locations
(indicated in brackets with a positive sign)
can be allocated to the signal states of the
following I/O module having the
appropriate type of signal or the diagnostics
information of diagnostic capable I/O
modules. This is done by configuring the
DI_0, - DI_DIA_0 DO_DIA_0
or
PE_DIA_0
modules for the relevant I/O
modules.
750-610 P-Supply,
2DIA(+30 BIT E),
DIA in E-PA
PE_DIA_16
Configuration module for 16 digital inputs,
2 bytes are reserved in the input process
image of the I/O controller. The bit
information in the first byte is allocated to
the 2 bit diagnostics data of the configured
supply module. Remaining bit locations
(indicated in brackets with a positive sign)
can be allocated to the signal states of the
following I/O module having the
appropriate type of signal or the diagnostics
information of diagnostic capable I/O
modules. This is done by configuring the
DI_0, - DI_DIA_0 DO_DIA_0
or
PE_DIA_0
modules for the relevant I/O
modules.
750-610 P-Supply,
2DIA(+14 BIT E),
DIA in E-PA