WAGO-TO-PASS® 761
Device Description
19
761-210 Telecontrol Module Compact
Manual
Version 2.0.0
3.4.2
Operating Voltage
Use SELV/PELV power source only!
The
TO-PASS
®
telecontrol module must only be powered from a PELV
(Protective Extra Low Voltage) or SELV (Safety Extra Low Voltage) power
source complying with the limited power source (LPS) requirements per DIN EN
60950-1.
Table 4: Terminal assignment for operating voltage
Figure 3: Terminal assignment for operating voltage
Connection
Short name
Designation
1,2
Uv
Operating voltage (+) DC +10 … 30 V
3, 4
GND
Operating voltage (-) DC 0 V, Ground
38
Shield
Enclosure screening, connection of the PE
Connect the shield connection to the DIN rail!
The shield connection of the
TO-PASS
®
telecontrol module (shield, terminal 38)
must be connected to the DIN rail. The DIN rail must have a low-impedance
ground (see section "Connections" > "Ground").