3.6.6
Climatic Environmental Conditions
Table 16: Technical Data – Climatic Environmental Conditions
Surrounding air temperature, operation 0 °C … 55 °C
Surrounding air temperature, storage
−
25 °C … +85 °C
Operating altitude
0 … 2000 m
Relative humidity
Max. 5 % … 95 % without condensation
Pollution degree
2
Protection type
IP20
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
• Ensure that additional measures for
components are taken, which are
used in an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
• Ensure that the permissible
temperature range of the connecting
cable is correct dimensioned
depending on the installation
position and current intensity,
because the clamping point
temperature at 10 A can be up to
25 °C above the expected
surrounding air temperature.